ENERJOY I Design & Sizing
                  Use the chart below  to size your rooms.   
                  Design Guidelines 
                  
1)    Determine panel size by selecting a balanced  combination of ENERJOY Peopleheaters to cover 10% of the ceiling surface.
                    
                    2)    Design symmetrical Heatmodule placement in the  same way you locate lights to illuminate a room, recognizing areas of high heat  loss and special comfort areas.
                    
                    3)    Take full advantage of the broad dispersion of  radiant energy emanating at a 80° angle from the Heatmodule surface. It is  all right to oversize[1] by using identical heatmodules to attain symmetry even  though the sizing chart calls for unequal or smaller units.
                  Rules of Thumb:
                  1) Select a geometrically pleasing design,  while allowing a 2' to 4' set off [2] from exterior walls and figuring approximately  two times the setoff distance between Heatmodules. 
                  2) Use the following general  specifications to determine watts per square foot (W/SF) of room area:  Bath areas: 7  W/SF; Living room or corner offices: 6 W/SF; Dens, offices, dining rooms or corner  bedrooms: 5W/SF; Kitchens or middle bedrooms: 4 W/SF.  Above 7,000 degree  days add 1 W/SF.
                                      [1]The sizing increase or decrease determines cycle frequency- how quickly  the thermostat setpoint is satisfied.
                                      [2]There is no set off restriction.   Unnecessary heat loss is  minimized
                  ENERJOY I  Heatmodule Selection
                                      (for  additional wattages, refer to ENERJOY I specification section)
                  
                    
                      
                        Room (typical)   | 
                        Size    (feet)  | 
                        Area    (SQ.FT.)  | 
                        New    Construction 
                          (8' ceilings)  | 
                        Thermostat  | 
                      
                      
                        Closet/powder  | 
                        4 x 5  | 
                        20-30  | 
                        22RCL    or 22RCLFL  | 
                        1  | 
                      
                      
                        Standard    bath  | 
                        5 x 7  | 
                        35-50  | 
                        23RCL, 23RCH, 24RCL, 23RCLFL, or 24RCHFL  | 
                        1  | 
                      
                      
                        Large    bath  | 
                        8 x    10  | 
                        75-100  | 
                        25RCL, 25RCH, 26RCL, 25RCLFL or 26RCHFL  | 
                        1  | 
                      
                      
                        Den/office  | 
                        8 x    10  | 
                        75-100  | 
                        24RCL    or 25RCL  | 
                        1  | 
                      
                      
                        Corner    bed  | 
                        12 x    12  | 
                        130-160  | 
                        28RCL    or 2-24RCL  | 
                        1  | 
                      
                      
                        Middle    bed  | 
                        12 x    12  | 
                        130-160  | 
                        26RCL  | 
                        1  | 
                      
                      
                        Lg.    Corner bed  | 
                        13 x    15  | 
                        170-210  | 
                        2-25RCL,    2-25RCH or 2-26RCL  | 
                        1  | 
                      
                      
                        Lg.    Middle bed  | 
                        13 x    15  | 
                        170-210  | 
                        28RCL    or 2-24RCL  | 
                        1  | 
                      
                      
                        Standard    Kit.  | 
                        9 x    12  | 
                        150-180  | 
                        24RP  | 
                        1  | 
                      
                      
                        Lg.    Kitchen  | 
                        11 x    15  | 
                        150-18  | 
                        26RCL    or 2-23RCL  | 
                        1  | 
                      
                      
                        Stand.    Dining  | 
                        8 x    12  | 
                        90-120  | 
                        25RCL,    26RCL or 2-23RCL  | 
                        1  | 
                      
                      
                        Lg.    Dining  | 
                        12 x    14  | 
                        150-190  | 
                        28RCL    or 2-24RCL  | 
                        1  | 
                      
                      
                        Stand.    Living  | 
                        12 x    15  | 
                        160-200  | 
                        2-26RCL  | 
                        1  | 
                      
                      
                        Lg.    Living  | 
                        14 x    20  | 
                        260-300  | 
                        3-28RCL  | 
                        1  | 
                      
                      
                        Wiring note: Existing 20 amp 120 volt lighting circuits    may serve ENERJOY I Heatmodules.  | 
                      
                      
                        Insulation note:  Insulate floor above basement or    crawlspace.  | 
                      
                    
                   
                  Additional Guidelines:
                    
                      Supplemental heating:   basements and super-insulated houses- Use 1-24RCL for each 100 sq. ft. of  space--approx. 3-4 W/SF.
                  Cathedral ceilings or 10'  ceilings: 
  For 12' peak (avg. 10') increase heat panel area by 25%.  Ex.- Use 28RCL instead  of 26RCL. 
  For 16' peak (avg. 12') increase heat panel size by 50%. 
                  Split Levelbuildings- Add  one watt per square foot.
                  Fireplaces, sliders or  skylights- Add one watt per square foot.
                  Typical  ENERJOY® Sizing Examples
                                      MODEL ENERGY CODE SPECIFICATIONS:
                    Operative Temperature 70°F
                  BUILDING SPECS: Room  Dimensions:15 x 15 x 8; Wall: R-19; Floor: R-19; Ceiling: R-38; Glass: R-2  (graphs assume window size of 3’x4’ & Sliding glass doors of 6’x6’8”); Air  changes per hour: 0.25. 
                      CHART USAGE: 1) Compute window percentage of outside wall;  2) Find intersection with Design Temperature; 3) Select ENERJOYHeatmodule(s) to meet wattage. 
                      PLACEMENT: Parallel to and centered with 2’ offset from outside  wall; second panel, if required, will be aligned with the first and separated  approximately 4’ to 6’, or the distance necessary to achieve geometric layout  balance
                      
                      1.  MIDDLE ROOM – 1 OUTSIDE WALL 
                      
                      
 
                   
                  Possible ENERJOY Selections: 
                  
                    - 1 Window, 5°F – 700watts    1       - 27RCL 700watt Heatmodule 
 
                    - 2 Windows, -15°F – 1100watts           2 - 26RCL 600watt Heatmodules 
 
                    - 1 Slider, -15°F – 1250watts           2 - 26RCL 600watt Heatmodules 
 
                    - 1 Slider, 5°F – 950watts           1 - 28RCH 1000watt Heatmodule
 
                  
                   
                  2. CORNER ROOM –  2 OUTSIDE WALLS
                      
 
                   
                  Possible ENERJOY Selections: 
                  
                    - 2 Window, 5°F – 800 Watts          2 - 24RCL 400watt Heatmodules 
 
                    - 2 Windows, -15°F – 1100w    2       - 26RCL 600watt Heatmodules 
 
                    - 4 Windows, 5°F – 1000watt    2       - 25RCL 500wtt Heatmodules 
 
                    - 4 Windows, -15°F – 1250watt          2 - 26RCL 600watt Heatmodules 
 
                    - 2 Windows & 1 Slider  5°F - 1000watt , 2 – 25RCL       500watt Heatmodules 
                                         -15°F – 1300watt, 2 – 27RCL 700watt Heatmodules 
                  
                  For assistance, call 800 544  5182.  If you have a floor plan fax us at  860 399-6460 or email info@sshcinc.com.